New Product
Terminal Relay
G6D-F4PU/G3DZ-F4PU (Push-In Plus Technology)
G6D-F4B/G3DZ-F4B (Screw Terminal)
Model with Push-In Plus technology Added
to Terminal Relays
with Four-point Output Lineup
G6D-F4B
G3DZ-F4B
G6D-F4PU
G3DZ-F4PU
• Realized 5 A rating by optimal designs for wide variety of applications
(Push-In Plus technology).
• Push-In Plus terminal enables work reduction and requires no
retightening.
• Short Bars (order separately) ensure easy common wiring and
crossover wiring to adjacent terminal relays.
• Double wire method enables branch wiring (Push-In Plus technology)
• Each relay has independent coils and contacts for PLC output
compatible (both NPN and PNP).
• Mechanical Relay models and power MOS FET relay models
For the most recent information on models that have been
(for high frequency contact ratings) are available.
certified for safety standards, refer to your OMRON website.
• LED operation indicator, diode for coil surge absorption, and tools for
Refer to Safety Precautions on page 12.
easy removal of relays are included as standard equipment.
• UL and CSA certification for standard models.
VDE certification for Screws terminal, TÜV certification for Push-In Plus terminal.
IP20 protection code for Push-In Plus models.
Features (G6D-F4PU/G3DZ-F4PU (Model with Push-In Plus technology))
Pursuing High Usability
Slimmer Width Yet Larger Power Supply Capacity
Short Bars enable common wiring
Rated load: 3A
Larger
current
capacity by
approx.
Easy common wiring with Short Bars
Tools for
removal
LED operation
indicator
Rated load: 5A
Slimmer
width by
approx.
30%
67%
Independent circuit for PLC output
in both NPN and PNP
*
Branch wiring with double wire
method
Wide Variety of Application
Width: 31 mm
G6D-F4B
(Screw)
Rated load: 5A
Width: 31 mm
G6D-F4PU
(Push-In Plus technology)
Width: 43 mm
G6B-4BND
(Screw)
NEW
Applicable to Various Number of I/O Points
Short Hight for Installation in Narrow Spaces
Operating panel of each device, etc.
Connector terminal box, etc.
G2RV-SR
G6D-F4PU
1 point
4 point
G2RV-SR
G70V
8 point
16 point
Control box, etc.
* Value Design for Panel
Our shared concept “Value Design for Panel” for the specifications of products used in control panels (hereinafter called “Value Design”) will create new
value to your control panels. Combining multiple products that share the Value Design concept will further increase the value provided to control panels.
1
G6D-F4PU/G3DZ-F4PU/G6D-F4B/G3DZ-F4B
Ordering Information
When your order, specify the rated voltage.
Main unit
Model with Push-In Plus technology
Mounted Relay type
Contact form
Model
12 VDC
G6D-F4PU
Mechanical Relay
24 VDC
SPST x 4
(1NO x 4)
12 VDC
G3DZ-F4PU
Power MOS FET relay
Operation coil ratings
24 VDC
Model with Screw Terminal
Mounted Relay type
Contact form
Model
12 VDC
G6D-F4B
Mechanical Relay models
24 VDC
SPST x 4
(1NO x 4)
12 VDC
G3DZ-F4B
Power MOS FET relay
Operation coil ratings
24 VDC
Accessories (Order Separately)
zConnection socket (single sales available)
G6D-F4PU/G3DZ-F4PU (Model with Push-In Plus technology)
Model
Operation coil ratings
12 VDC
P6DF-F4PU
24 VDC
G6D-F4B/G3DZ-F4B (Models with Screw terminal)
Model
Operation coil ratings
12 VDC
P6DF-F4B
24 VDC
Note: 1. Connection socket P6DF-F4B as a single part is not certified by safety standards individually.
2. Single socket which does not mount a relay (with cover)
.
zShort Bar (G6D-F4PU/G3DZ-F4PU (Model with Push-In Plus technology))
Pitch
Applicable models
Number of
poles
Color
PYDN-7.75-020@
2
7.75 mm
G6D-F4PU
G3DZ-F4PU
P6DF-F4PU
3
4
20
Model*1
Red (R)
Blue (S)
Yellow (Y)
PYDN-7.75-030@
PYDN-7.75-040@
PYDN-7.75-200@
Note: Use the Short Bars for crossover wiring within one Socket or between Sockets.
*1. Replace the box (@) in the model number with the code for the covering color. Selection of the box (@): R=Red, S=Blue, Y=Yellow
zShort Bar (G6D-F4B/G3DZ-F4B (Model with Screw Terminal))
Applicable Terminal
Relay Model
G6D-F4B
G3DZ-F4B
2
Model
G6D-4-SB
G6D-F4PU/G3DZ-F4PU/G6D-F4B/G3DZ-F4B
zReplacement Relay (G6D-F4PU/G3DZ-F4PU (Model with Push-In Plus technology))
Applicable Terminal Relay Model
Model
G6D-F4PU/G6D-F4B
G6D-1A-ASI
G3DZ-F4PU/G3DZ-F4B
G3DZ-2R6PL
Operation coil ratings
12 VDC
24 VDC
12 VDC
24 VDC
zParts for DIN Track Mounting
Appearance
Model
Type
1m
PFP-100N
0.5 m
PFP-50N
DIN Tracks
End Plate *1
PFP-M
Spacer
PFP-S
*1. When mounting support rail, please use End Plate (Model PFP-M).
3
G6D-F4PU/G3DZ-F4PU/G6D-F4B/G3DZ-F4B
Ratings/Specifications
Ratings
Characteristics
zRelay Specification
Coil Ratings (per G6D Relay)
Operation
coil rating
DC
12
24
Rated
current
(mA)
Coil
resistance
(Ω)
18.7
10.5
720
2,880
Item
Must
operate
voltage
(V)
Must
release
voltage
(V)
Max.
voltage
(V)
70%
max.*
10%
min.
130%
Power
consump
tion
(mW)
Approx.
200
Note: 1. Rated current and coil resistance were measured at a coil
temperature of 23°C with a tolerance of ±20%.
2. Performance characteristic data are measured at a coil
temperature of 23°C.
3. The maximum allowable voltage is the maximum value of
the operating voltage for the relay coil operating power
supply. There is no continuous allowance.
4. The rated current includes the terminal’s LED current.
* The must operate voltage is 75% or less of the rated voltage if the
relay is mounted in the upside down.
Contact Ratings (per G6D Relay)
G6D-F4PU (Model with Push-In Plus technology)
Item
G6D-F4PU
(Model with Push-In Plus technology)
Model
Load
Relay output
Contact resistance *1
100 mΩ max.
Operate time *2
10 ms max.
Release time *2
10 ms max.
Insulation resistance
Dielectric
strength
1,000 MΩ min. (at 500 VDC)
Between coil and
contacts
Between contacts
of the same polarity 750 VAC, 50/60 Hz for 1 min
Shock resistance voltage
(between coil and contacts)
Vibration resistance
Shock
resistance
2,000 VAC, 50/60 Hz for 1 min
4,000 V (1.2 × 50 μs)
Destruction
10 to 55 to 10 Hz, 0.75-mm single amplitude
(1.5-mm double amplitude)
Malfunction
10 to 55 to 10 Hz, 0.75-mm single amplitude
(1.5-mm double amplitude)
Destruction
500 m/s2
Malfunction
100 m/s2
Mechanical
20,000,000 operations min.
(switching frequency: 18,000 operations/hr)
Electrical *2
70,000 operations min.
(5 A at 250 VAC, resistive load)
70,000 operations min.
(5 A at 30 VDC, resistive load)
(at 1,800 switching frequencies/hr)
Endurance
Resistive load (cosφ = 1)
Rated load
5 A at 250 VAC, 5 A at 30 VDC
10 mA at 5 VDC
Rated carry current
Failure rate P Level
(reference value *3)
5A
Max. switching voltage
250 VAC, 30 VDC
Ambient operating temperature,
Ambient storage temperature
-25 to 55°C (with no icing)
Ambient operating humidity
45% to 85%
LED color
Yellow
Sealing
IP20
Weight
Approx. 95 g
Max. switching current
5A
Max. switching capacity
(reference value)
1,250 VA, 150 W
G6D-F4B (Model with Screw terminal)
Item
Load
Resistive load (cosφ = 1)
Rated load
3 A at 250 VAC, 3 A at 30 VDC
Rated carry current
5A
Max. switching voltage
250 VAC, 30 VDC
Max. switching current
5A
Max. switching capacity
(reference value)
1,250 VA, 150 W
Note: The data shown above are initial values.
*1. Measurement condition: 1 A at 5 VDC
*2. Ambient temperature condition: 23°C
*3. This value is measured at 120 switching frequencies/min.
G6D-F4B
(Model with Screw terminal)
Model
Item
Relay output
Contact resistance *1
100 mΩ max.
Operate time *2
10 ms max.
Release time *2
10 ms max.
Insulation resistance
Dielectric
strength
Between coil and
contacts
Between contacts
750 VAC, 50/60 Hz for 1 min
of the same polarity
Shock resistance voltage
(between coil and contacts)
Vibration resistance
Shock
resistance
1,000 MΩ min. (at 500 VDC)
2,000 VAC, 50/60 Hz for 1 min
4,000 V (1.2 × 50 μs)
Destruction
10 to 55 to 10 Hz, 0.75-mm single amplitude
(1.5-mm double amplitude)
Malfunction
10 to 55 to 10 Hz, 0.75-mm single amplitude
(1.5-mm double amplitude)
Destruction
500 m/s2
Malfunction
100 m/s2
Mechanical
20,000,000 operations min.
(switching frequency: 18,000 operations/hr)
Electrical *2
200,000 operations min.
(3 A at 250 VAC, resistive load)
200,000 operations min.
(3 A at 30 VDC, resistive load)
(at 1,800 switching frequencies/hr)
Endurance
Failure rate P Level
(reference value *3)
10 mA at 5 VDC
Ambient operating temperature,
Ambient storage temperature
-25 to 55°C (with no icing)
Ambient operating humidity
45% to 85%
LED color
Yellow
Sealing
---
Weight
Approx. 65 g
Note: The data shown above are initial values.
*1. Measurement condition: 1 A at 5 VDC
*2. Ambient temperature condition: 23°C
*3. This value is measured at 120 switching frequencies/min.
4
G6D-F4PU/G3DZ-F4PU/G6D-F4B/G3DZ-F4B
Ratings
Characteristics
zPower MOS FET Relay Specifications
G3DZ-F4PU
(Model with Push-In Plus technology)
Model
Input (per G3DZ Power MOS FET Relay)
Item
Rated
voltage
Operating
voltage
Must
Must
operate
release
voltage level voltage level
Input
impedance
Rated
current
12
9.6 to 14.4
VDC
9.6 VDC
max.
2 kΩ ±20%
8.0 mA
±20%
Power MOS FET relay output
Must operate time
10 ms max.
Release time
15 ms max.
Output ON-resistance
2.4 Ω max.
Leakage current at OFF state
10 μA max. (at 125 VDC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Note: The rated current includes the terminal’s LED current.
Dielectric strength between I/O
2,000 VAC, 50/60 Hz for 1 min
Output (per G3DZ Power MOS FET Relay)
Vibration resistance
10 to 55 to 10 Hz, 0.75-mm single
amplitude (1.5-mm double amplitude)
Shock resistance
500 m/s2
Ambient operating temperature,
Ambient storage temperature
-25 to 55°C (with no icing)
Ambient operating humidity
45% to 85%
LED color
Yellow
Sealing
IP20
Weight
Approx. 95 g
DC
24
19.2 to
28.8 VDC
Rated operating
voltage
5 to 240 VAC
5 to 100 VDC
19.2 VDC
max.
Load voltage
range
3 to 264 VAC
3 to 125 VDC
1 VDC min.
4 kΩ ±20%
Load current
100 μ to 0.3 A
Note: There is no output polarity for the G3DZ.
8.2 mA
±20%
Inrush current
resistance
6 A (10 ms)
G3DZ-F4B
(Model with Screw terminal)
Model
Item
Power MOS FET relay output
Must operate time
10 ms max.
Release time
15 ms max.
Output ON-resistance
2.4 Ω max.
Leakage current at OFF state
10 μA max. (at 125 VDC)
Insulation resistance
100 MΩ min. (at 500 VDC)
Dielectric strength between I/O
2,000 VAC, 50/60 Hz for 1 min
Vibration resistance
10 to 55 to 10 Hz, 0.75-mm single
amplitude (1.5-mm double amplitude)
Shock resistance
500 m/s2
Ambient operating temperature,
Ambient storage temperature
-25 to 55°C (with no icing)
Ambient operating humidity
45% to 85%
LED color
Yellow
Sealing
---
Weight
Approx. 65 g
5
G6D-F4PU/G3DZ-F4PU/G6D-F4B/G3DZ-F4B
Ratings for Safety Standard Certification
The rated values for safety standard certification are not the same as individually defined performance values. Always check the specifications before use.
G6D-F4PU/G3DZ-F4PU
zUL-certified Models (File No. E41515)
Model
Standard
number
Category
Listed/
Recognition
Classification
Operating
coil ratings
Number
of poles
Contact ratings
Rated load voltage
250 VAC
30 VDC
G6D-F4PU
NRNT/7
Load Current, General Use and Resistive
5 A at 40°C
Listed
12 VDC
24 VDC
UL508
4
Rated load voltage
5-240 VAC
5-100 VDC
G3DZ-F4PU
Certified number of operations
Mechanical
20,000,000 operations min.
(at 18,000 switching
frequencies/hr)
Electrical
70,000 operations (5 A at 250
VAC, resistive load)
70,000 operations (5 A at 30
VDC, resistive load)
(at 1,800 switching
frequencies/hr)
---
Load Current, General Use and Resistive
0.3 A at 55°C
P6DF-F4PU
SWIV2
Contact terminal
5 A, 250 V
Recognition
---
zCSA-certified Models (File No. LR35535)
Model
P6DF-F4PU
Standard number
Operating
coil ratings
Class number
CLASS 3211 07
CLASS 3211 87
C22.2 NO. 14
12 VDC
24 VDC
Number
of poles
4
Contact ratings
Contact terminal
5 A, 250 V
zTÜV Rheinland Certification (Certification No.R50429253)
Model
G6D-F4PU
Operating
Coil ratings
12 VDC
24 VDC
Number
of poles
4
Contact ratings
Rated load voltage
250 VAC
30 VDC
Load Current, General Use and Resistive
5 A at 40°C
Certified number of operations
Mechanical
1,000,000 operations
(at 18,000 switching
frequencies/hr)
Electrical
70,000 operations (5 A at 250
VAC, resistive load)
70,000 operations (5 A at 30
VDC, resistive load)
(at 1,800 switching
frequencies/hr)
zTÜV Rheinland Certification (Certification No.R50429249)
Model
G3DZ-F4PU
Operating
Coil ratings
12 VDC
24 VDC
Number
of poles
4
Contact ratings
Rated load voltage
5-240 VAC
5-100 VDC
Certified number of operations
---
Load Current, General Use and Resistive
0.3 A at 55°C
zTÜV Rheinland Certification (Certification No.50429224)
Model
P6DF-F4PU
6
Operating
Coil ratings
12 VDC
24 VDC
Number
of poles
4
Contact ratings
Contact terminal
5 A, 250 V
Certified number of operations
---
Certified number of operations
---
G6D-F4PU/G3DZ-F4PU/G6D-F4B/G3DZ-F4B
G6D-F4B/G3DZ-F4B
zUL-certified Models (File No. E87929)
Model
Standard
number
Category
Listed/
Recognition
Classification
Operating
coil ratings
Number
of poles
Contact ratings
Rated load voltage
250 VAC
30 VDC
G6D-F4B
UL508
SWIV2
Recognition
12 VDC
24 VDC
Certified number of operations
---
Load Current
5 A, Resistive
4
Rated load voltage
3-264 VAC
3-125 VDC
G3DZ-F4B
---
Load Current
0.3 A
zCSA-certified Models (File No. LR35535)
Model
Standard number
Class number
Operating
coil ratings
Number
of poles
Contact ratings
Rated load voltage
250 VAC
30 VDC
G6D-F4B
CLASS 3211 07
CLASS 3211 87
C22.2 NO. 14
12 VDC
24 VDC
G3DZ-F4B
4
Certified number of operations
---
Load Current
5 A, Resistive
Rated load voltage
3-264 VAC
3-125 VDC
---
Load Current
0.3 A, Resistive
zVDE Certification (Certification No.40017757)
Model
G6D-F4B
Operating
coil ratings
12 VDC
24 VDC
Number
of poles
4
Contact ratings
Rated load voltage
250 VAC
24 VDC
Certified number of operations
---
Load Current
3A
zVDE Certification (Certification No.40046252)
Model
G3DZ-F4B
Operating
coil ratings
12 VDC
24 VDC
Number
of poles
4
Contact ratings
Rated load voltage
5-240 VAC
5-100 VDC
Certified number of operations
---
Load Current
0.3 A
zVDE Certification (Certification No.40046241)
Model
P6DF-F4B
Operating
coil ratings
12 VDC
24 VDC
Number
of poles
Contact ratings
Certified number of operations
Rated load voltage
250 VAC
4
--Load Current
0.3 A
7
G6D-F4PU/G3DZ-F4PU/G6D-F4B/G3DZ-F4B
Engineering Data
Engineering Data
zG6D-F4PU
Endurance Curve
100
Operation times (× 104 times)
Switching current (A)
Maximum Switching Capacity
50
30
10
5
3
DC resistive load
AC resistive
load
500
300
100
30
10
1
0.5
5
0.3
3
0.1
0
250 VAC, 30 VDC, Resistive load
50
3
5
10
30 50 100
250 500
250 VAC, 30 VDC, Inductive load
(cosФ=0.4 L/R=7 ms)
0
1
2
3
4
5
6
7
8
9
10
Switching current (A)
Switching voltage (V)
5
Load current (A)
Load current (A)
Load Current vs. Ambient Temperature
Load Current vs. Ambient Temperature
(Specifications with UL and TÜV
(Product specification)
certification)
4
5
4
3
3
2
2
1
1
0
-25 -20
0
20
40
55 60
80
0
-25-20
100
0
20
40 55 60
Ambient temperature (˚C)
80
100
Ambient temperature (˚C)
zG6D-F4B
100
50
30
10
5
3
DC resistive load
AC resistive
load
100
50
250 VAC, 30 VDC, Resistive load
30
5 250 VAC, 30 VDC, Inductive load
(cosФ=0.4 L/R=7 ms)
3
0.5
0.3
3
5
10
30 50 100
250 500
Switching voltage (V)
8
500
300
10
1
0.1
0
Endurance Curve
Operation times (× 104 times)
Switching current (A)
Maximum Switching Capacity
0
1
2
3
4
5
6
7
8
9
10
Switching current (A)
G6D-F4PU/G3DZ-F4PU/G6D-F4B/G3DZ-F4B
zG3DZ-F4PU
Load Current vs. Ambient Temperature Inrush current resistance
1
Inrush current (A.Peak)
Load current (A)
Non-repetitive
(Keep the inrush current to below the inrush current resistance
value (i.e., below the broken line) if it occurs repetitively.)
0.8
0.6
0.4
10
8
6
4
0.3
0.2
0
-25 -20
2
0
20
40
55 60
80
0
100
5
10
30 50
100
Ambient temperature (˚C)
300 500 1,000 3,000 5,000
Energizing time (ms)
Note: These data are actual measured
values that were sampled from the
production line and prepared in
graph format, and are for reference
purposes only.
A relay is manufactured by mass
production, and as a basic rule must
be used with allowance made for a
certain amount of deviation.
zG3DZ-F4B
Load Current vs. Ambient Temperature Inrush current resistance
1
Inrush current (A.Peak)
Load current (A)
Non-repetitive
(Keep the inrush current to below the inrush current resistance
value (i.e., below the broken line) if it occurs repetitively.)
0.8
0.6
0.4
10
8
6
4
0.3
0.2
0
-25 -20
2
0
20
40
55 60
80
100
Ambient temperature (˚C)
0
5
10
30 50
100
300 500 1,000
3,000 5,000
Energizing time (ms)
Note: These data are actual measured
values that were sampled from the
production line and prepared in
graph format, and are for reference
purposes only.
A relay is manufactured by mass
production, and as a basic rule must
be used with allowance made for a
certain amount of deviation.
9
G6D-F4PU/G3DZ-F4PU/G6D-F4B/G3DZ-F4B
Dimensions
(Unit: mm)
Main unit
G6D-F4PU
G3DZ-F4PU
LED operation indicator
2-4 dia. or 2-M3.5
IN side
+
3
7
+
2
6
2
+
1
5
3
+
4
108±0.3
OUT side
Tool for easy
removal of relays
Mounting Hole
Dimensions
31 max.
30
33.6
35 max.
Note: Pull out the
hooks to mount
the Relay with
screws.
Terminal Connection Examples
+
4
8
+
3
7
+
2
6
1
5
12
11
10
9
16
15
14
13
L4
L3
L2
L1
12
11
10
9
16
15
14
13
Note: 1. Pay utmost attention not to make
mistakes with the polarity of the
input terminals.
2. There is no output polarity for
G6D-F4PU/G3DZ-F4PU.
+
AC (DC power supply is
also available.)
Mounting Hole Dimensions
LED operation indicator
16-M3 Phillips screw
2-4 dia. or 2-M3.5
8.7
4
3
2
1
8
7
6
5
IN
68 max.
2
1
3
+
3
7
+
2
6
+
1
5
+
1
2
3
4
OUT side
12
11
10
9
16
15
14
13
31 max.
35 max.
23±0.3
Tool for easy removal of relays
Terminal Connection Examples
+
8
76±0.3
8.7
8
4
4
RY1 RY2 RY3 RY4
4
Terminal Arrangement/Internal
Connection Diagram
(Top View)
IN side
OUT
10
8
1
90.4 max.
100 max.
G6D-F4B
G3DZ-F4B
4
3
7
+
2
6
+
1
5
12
11
10
9
16
15
14
13
L4
L3
L2
L1
+
AC (DC power supply is
also available.)
12
11
10
9
16
15
14
13
Note: 1. Pay utmost attention not to make
mistakes with the polarity of the
input terminals.
2. There is no output polarity for
G6D-F4B/G3DZ-F4B.
G6D-F4PU/G3DZ-F4PU/G6D-F4B/G3DZ-F4B
Accessories (Order Separately)
zShort Bars
PYDN-7.75-@@ (7.75 mm)
Pitch
L
G6D-F4PU
G3DZ-F4PU
P6DF-F4PU
7.75 mm
18.5
12
2.25
Number
of poles
Applicable model
L (Length)
Color
3.90
2
15.1
3
22.85
4
30.6
20
154.6
Model*
PYDN-7.75-020@
Red (R)
Blue (S)
Yellow (Y)
PYDN-7.75-030@
PYDN-7.75-040@
PYDN-7.75-200@
* Replace the box (@) in the model number with the code for the covering color. Selection of the
box (@): R=Red, S=Blue, Y=Yellow
Note: Use the Short Bars for crossover wiring within one Socket or between Sockets.
1.57
zShort Bars
G6D-4-SB
7.62
7.62
7.62
5.7
3.7
5
9.6
(28.56)
2.6
zParts for DIN Track Mounting
DIN Tracks
PFP-100N
PFP-50N
7.3±0.15
4.5
35±0.3
15
25
10
25
25
10
25
15 (5)*
1,000 (500)*
End Plate
PFP-M
27±0.15
1
* () indicates the dimension of PFP-50N.
10
6.2
M4 × 8
Pan head
screw
1.8
1
50
35.5 35.3
1.8
11.5
10
M4 Spring washer
Spacer
PFP-S
1.3
4.8
16
12
5
34.8
44.3
16.5
11
G6D-F4PU/G3DZ-F4PU/G6D-F4B/G3DZ-F4B
Safety Precautions
Be sure to read the Common Precautions for All Relays in the website.
Warning Indications
Precautions
for Safe Use
Supplementary comments on what to do or
avoid doing, to use the product safely.
Precautions
for Correct
Use
Supplementary comments on what to do or
avoid doing, to prevent failure to operate,
malfunction, or undesirable effects on product
performance.
Precautions for Safe Use
zTransport
• Do not transport the I/O Relay Terminal under the following
locations. Doing so may occasionally result in damage,
malfunction, or deterioration of performance characteristics.
• Locations subject to water or oil
• Locations subject to high temperature or high humidity
• Locations subject to condensation as the result of rapid changes
in temperature.
• Do not transport a Socket when it is not packaged.
Damage or failure may occur.
zOperating and Storage Environments
• Do not use or store the I/O Relay Terminal in the following
locations. Doing so may result in damage, malfunction, or
deterioration of performance characteristics.
• Locations subject to rainwater or water splashes.
• Locations subject to exposure to water, oil, or chemicals.
• Locations subject to high temperature or high humidity.
• Storage at locations subject to ambient temperatures outside the
range -25 to 55°C
• Usage at locations subject to ambient temperatures outside the
range -25 to 55°C
• Locations subject to relative humidity outside the range 45% to
85%
• Locations subject to condensation as the result of rapid changes
in temperature.
• Locations subject to corrosive or flammable gases.
• Locations subject to dust, salts, or iron, or locations where there
is salt damage
• Locations subject to direct sunlight.
• Locations subject to shock or vibration.
zInstallation and Mounting
• Mount the I/O Relay Terminal in the specified direction. Otherwise
excessive heat generated by the I/O Relay Terminal may
occasionally cause burning.
Mounting Directions
• Mount the I/O Relay Terminal firmly to a DIN Track. Otherwise, the
I/O Relay Terminal may fall off.
• Do not handle the I/O Relay Terminal with oily or dusty (especially
iron dust) hands.
• Make sure that there is no excessive ambient temperature rise due
to the heat generation of the I/O Relay Terminal. If the I/O Relay
Terminal is mounted inside a panel, install a fan so that the interior
of the panel is fully ventilated.
12
zInstallation and Wiring
• Use wires that are suited to the load current and voltage.
Otherwise, excessive heat generated by the wires may cause
burning or may cause the wire covering to melt, possibly leading to
electric shock.
• Do not use wires with a damaged outer covering. it may result in
electric shock or ground leakage.it may result in electric shock or
ground leakage.
• Do not wire any wiring in the same duct or conduit as power or
high-tension lines. Inductive noise may damage the I/O Relay
Terminal or cause it to malfunction.
• Do not apply a voltage or current that exceeds the rating to any
terminal. Doing so may result in failure or burning.
• Do not use a deforming Short Bars. Doing so may result in
damage, malfunction, or deterioration of performance
characteristics.
zPush-In Plus Terminal
• Do not wire anything to the release holes.
• Do not tilt or twist the screwdriver while it is inserted into a release
hole on the terminal. The terminal may be damaged.
• Insert a flat-blade screwdriver into the release holes at an angle.
The terminal may be damaged if you insert the screwdriver straight
in.
• Do not allow the flat-blade screwdriver to fall out while it is inserted
into a release hole.
• Do not bend a wire past its natural bending radius or pull on it with
excessive force. Doing so may cause the wire disconnection.
• Do not insert more than one wire into each terminal insertion hole.
• To prevent wire materials from smoking or ignition, confirm wire
ratings and use the wiring materials given in the following table.
Recommended wires
0.5 to 1.5 mm2/AWG20 to 16
Stripping length
(Ferrules not used)
8 mm
zApplication
• Select a load within the rated values. Not doing so may result in
malfunction, failure, or burning.
• The G6D may occasionally rupture if short-circuit current flows. As
protection against accidents due to short-circuiting, be sure to
install protective devices, such as fuses and no-fuse breakers, on
the power supply side.
• Use a power supply within the rated frequencies. Otherwise,
malfunction, failure, or burning may occasionally occur.
• Minor electrical shock may occasionally occur if you touch the
power charging area such as the terminal wiring area. Always turn
OFF the power supply before performing wiring.
G6D-F4PU/G3DZ-F4PU/G6D-F4B/G3DZ-F4B
• Insert Short Bars so that the protrusion part of a Short Bar comes
to the wire insertion side. If the Short Bar is inserted in the upside
down direction, the Short Bar may not be inserted securely.
NG
OK
Precautions for Correct Use
• Do not drop the Socket or subject it to abnormal vibration or shock
during transportation or mounting. Doing so may result in
deterioration of performance, malfunction, or failure.
• Use a power supply with low noise.
z G6D-F4PU/G3DZ-F4PU (Model with Push-In
Plus technology)
1. Connecting Wires to the Push-In Plus Terminal
Part Names of the Terminal
Short bar insertion hole
Release hole
Terminal (insertion) hole
Connecting Wires with Ferrules and Solid Wires
Insert the solid wire or ferrule straight into the terminal until the end
strikes the terminal.
zRecommended Ferrules and Crimp Tools
Recommended ferrules
Applicable
wire
Stripping
Recommended ferrules
Ferrules
length
Conductor
[mm]
Manufactured Manufactured
length
Manufactured
(Ferrules by Phoenix
by
(mm2) (AWG)
(mm)
by Wago
used)
Contact
Weidmuller
0.25
0.34
24
22
0.5
20
0.75
18
1/1.25 18/17
1.25/1.5 17/16
8
10 AI0,25-8
10
12 AI0,25-10
8
10 AI0,34-8
10
12 AI0,34-10
H0.25/12
--H0.34/12
---
FE-0.25-8N-YE
--FE-0.34-8N-TQ
---
8
10 AI0,5-8
H0.5/14
FE-0.5-8N-WH
10
12 AI0,5-10
H0.5/16
FE-0.5-10N-WH
8
10 AI0,75-8
H0.75/14
FE-0.75-8N-GY
10
12 AI0,75-10
H0.75/16
FE-0.75-10N-GY
10 AI1-8
H1.0/14
FE-1.0-8N-RD
10
12 AI1-10
H1.0/16
FE-1.0-10N-RD
8
10 AI1,5-8
H1.5/14
FE-1.5-8N-BK
10
12 AI1,5-10
H1.5/16
FE-1.5-10N-BK
8
Recommended crimp tool
CRIMPFOX6
CRIMPFOX6T-F PZ6 roto
CRIMPFOX10S
Ferrules or solid wires
• If a wire is difficult to connect because it is too thin, use a flat-blade
screwdriver in the same way as when connecting stranded wire.
Connecting Stranded Wires
Use the following procedure to connect the wires to the terminal.
1. Hold a flat-blade screwdriver at an angle and insert it into the
release hole.
The angle should be between 10° and 15°. If the flat-blade
screwdriver is inserted correctly, you will feel the spring in the
release hole.
2. With the flat-blade screwdriver still inserted into the release hole,
insert the wire into the terminal hole until it strikes the terminal.
3. Remove the flat-blade screwdriver from the release hole.
(1)
(3)
Flat-blade
screwdriver
(3)
(1)
Variocrimp4
Note: 1. Make sure that the outer diameter of the wire coating is
smaller than the inner diameter of the insulation sleeve of
the recommended ferrule.
2. Make sure that the ferrule processing dimensions conform
to the following figures.
8 to 10 mm
1.9 mm max.
Release hole
Terminal (insertion) hole
2.6 mm max.
10° to 15°
(2)
(2)
Stranded wires
Checking Connections
• After the insertion, pull gently on the wire to make sure that it will
not come off and the wire is securely fastened to the terminal.
• To prevent short circuits, insert the stripped part of a stranded or
solid wire or the conductor part of a ferrule until it is hidden inside
the terminal insertion hole.
• If you use recommended ferrules, part of the conductor may be
visible after the ferrule is inserted into the terminal, but the product
insulation distance will still be satisfied.
3. Wires of AWG24 to AWG22/0.25 mm2 to 0.34 mm2 are not
certified by UL standard.
4. Do not connect a ferrule for the applicable wires (AWG17 to
AWG16/1.25 mm2 to 1.5 mm2) with an adjacent terminal
insertion hole.
13
G6D-F4PU/G3DZ-F4PU/G6D-F4B/G3DZ-F4B
2. Removing Wires from the Push-In Plus Terminal
Use the following procedure to remove wires from the terminal.
The same method is used to remove stranded wires, solid wires, and
ferrules.
1. Hold a flat-blade screwdriver at an angle and insert it into the
release hole.
2. With the flat-blade screwdriver still inserted into the release hole,
remove the wire from the terminal insertion hole.
3. Remove the flat-blade screwdriver from the release hole.
(1)
(3)
zRelay Replacement
• Use the Relay Removal Tool provided with the Unit to dismount a
Terminal Relay.
• Always turn OFF the power supply before replacing Relays.
• When mounting Relays, take care to vertically insert the sockets of
relays into the contact pins properly.
• Relays with other models or other voltages cannot be mounted
together.
Flat-blade screwdriver
(3)
(1)
10° to 15°
(2)
(2)
Wire
Recommended Flat-blade Screwdriver
Use a flat-blade screwdriver to connect and remove wires.
Use the following flat-blade screwdriver.
The following table shows manufacturers and models as of 2018/Dec.
Side
Front
2.5 mm dia.
Example: G6D-F4PU
zRemoving the Terminal Cover (G6D-F4B)
0.4 mm
Hold the base side of the terminal cover as shown in the diagram, and
remove the terminal cover by pulling it in upward.
2.5 mm
Model
Manufacturer
ESD 0,40×2,5
Wera
SZS 0,4×2,5
SZF 0-0,4×2,5 *
Phoenix Contact
0.4×2.5×75 302
Wiha
AEF.2,5×75
Facom
210-719
Wago
SDIS 0.4×2.5×75
Weidmuller
9900 (-2.5 × 75)
Vessel
* OMRON’s exclusive purchase model XW4Z-00B is available to
order as SZF 0-0,4×2,5 (manufactured by Phoenix Contact).
zMountable Relays
Relays and SSRs cannot be mounted together.
14
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have
any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing
by Omron). Omron disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE
PRODUCTS. BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE PRODUCTS WILL
SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the Products
or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at Omron’s election,
to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or replacement thereof) the
non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount equal to the purchase price
of the non-complying Product; provided that in no event shall Omron be responsible for warranty, repair, indemnity or any other
claims or expenses regarding the Products unless Omron’s analysis confirms that the Products were properly handled, stored,
installed and maintained and not subject to contamination, abuse, misuse or inappropriate modification. Return of any Products by
Buyer must be approved in writing by Omron before shipment. Omron Companies shall not be liable for the suitability or
unsuitability or the results from the use of Products in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any advice, recommendations or information given orally or in
writing, are not to be construed as an amendment or addition to the above warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself is
not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine, system,
or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product with
respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate it
to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice
to change part numbers when published ratings or features are changed, or when significant construction changes are made.
However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers may be
assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at any time to
confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
OMRON Corporation
Industrial Automation Company
Authorized Distributor:
Kyoto, JAPAN
Contact: www.ia.omron.com
Regional Headquarters
OMRON EUROPE B.V.
Wegalaan 67-69, 2132 JD Hoofddorp
The Netherlands
Tel: (31)2356-81-300/Fax: (31)2356-81-388
OMRON ELECTRONICS LLC
2895 Greenspoint Parkway, Suite 200
Hoffman Estates, IL 60169 U.S.A.
Tel: (1) 847-843-7900/Fax: (1) 847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark,
Singapore 119967
Tel: (65) 6835-3011/Fax: (65) 6835-2711
OMRON (CHINA) CO., LTD.
Room 2211, Bank of China Tower,
200 Yin Cheng Zhong Road,
PuDong New Area, Shanghai, 200120, China
Tel: (86) 21-5037-2222/Fax: (86) 21-5037-2200
© OMRON Corporation 2019 All Rights Reserved.
In the interest of product improvement,
specifications are subject to change without notice.
CSM_1_1_0319
Cat. No. J228-E1-01
0319(0319)